Most plant transmitters send a 4 to 20 mA signal where 4 mA is the bottom of the range (LRV) and 20 mA is the top (URV). Use this to check what the PLC or SCADA should show for a current you measure, or what current to expect for a process value. It also flags currents that NAMUR NE43 treats as a failure.
mA to Engineering Units
Formula
% of span = (mA - 4) / 16 x 100 Process value = LRV + (% of span / 100) x (URV - LRV) Square root (DP flow): Flow fraction = square root of (mA - 4) / 16 NAMUR NE43: valid 3.8 to 20.5 mA; failure at or below 3.6 mA or at or above 21.0 mA
Inputs used
- Lower range value (LRV, at 4 mA) (EU)
- Upper range value (URV, at 20 mA) (EU)
- Measured loop current (mA)
- Transmitter output
Worked example (fictional plant data)
- Level transmitter ranged 0 to 20 ft reads 13.6 mA
- % of span = (13.6 - 4) / 16 x 100 = 60.00%
- Level = 0 + 0.60 x (20 - 0) = 12.000 ft
- Voltage across a 250 Ω input resistor = 13.6 x 0.25 = 3.400 V
Engineering Units to mA
Formula
mA = 4 + 16 x (Value - LRV) / (URV - LRV) Square root (DP flow): mA = 4 + 16 x (flow fraction)²
Inputs used
- Lower range value (LRV, at 4 mA) (EU)
- Upper range value (URV, at 20 mA) (EU)
- Process value (EU)
- Transmitter output
Worked example (fictional plant data)
- % of span = (12 - 0) / (20 - 0) x 100 = 60.00%
- mA = 4 + 16 x 0.60 = 13.600 mA
Cautions
- Measure loop current with a meter in series, or across a known resistor. Do not break a loop that controls equipment without coordinating with operations.
- Not every transmitter follows NE43. Check the manual for its own failure currents (some use 3.75 mA and 21.75 mA) and set SCADA alarms to match.
- Square root scaling must be done once only: in the transmitter or in the PLC, never both.
- With square root scaling, very low DP signals are noisy. Most systems use a low flow cutoff (often 1 to 6% of flow).
References
- NAMUR Recommendation NE 43, Standardization of the signal level for the failure information of digital transmitters.
- ANSI/ISA-50.00.01, Compatibility of analog signals for electronic industrial process instruments (4-20 mA).
Results are estimates for operator and technician use. Equations follow the references above; always check against the instrument manual, your calibration procedure and plant data.
This calculator also appears on ActivatedSludge.com, our consulting site. Results are for training and operator use; always follow your plant’s procedures.